PVC covered copper conductor BS (British Standard)

PVC covered Copper conductor

according BS 6485

Conductors: Hard drawn round copper multiwire conductor
acc. to BS 7884:1997
Insulation: PVC compound type TI1 acc. to BS 7655-3.1, coloured black for type 8
or green for type 16
nominal
cross
section
no.
of
wire
wire
diameter
cond.
diameter
appr.
breaking
force
calc. conductor
resistance
at 20°C
appr.
weight
of cable
  mm²   mm mm kN Ohm/km kg/km
type 8
(thickness of insulation = 0,8 mm)
100562 14 7 1.60 6.6 5.7 1.3030 155
100560 16 7 1.70 6.9 5.9 1.1540 170
100563 16 3 2.65 7.3 6.6 1.1060 180
100561 32 7 2.46 9.2 12.4 0.5497 335
100564 32 3 3.75 9.7 12.7 0.5520 337
100565 70 7 3.55 12.3 26.9 0.2646 680
             
type 16
(thickness of insulation = 1,6 mm)
100571 16 7 1.70 8.5 5.9 1.1540 200
100572 16 3 2.65 8.9 6.6 1.1060 205
100573 32 7 2.46 10.8 12.4 0.5497 374
100574 32 3 3.75 11.3 12.7 0.5520 380
100575 70 7 3.55 13.9 26.9 0.2646 725

→ Other cross-sections on request.